p0151
Terminal Module component number / TM comp_no
TM150, TM31,
Can be changed: C1(4)
TM54F_MA,
Data type: Unsigned8
TM54F_SL
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Sets the component number for the Terminal Module.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a Terminal Module.
p0151[0...n]
Voltage Sensing Module component number / VSM comp_no
VECTOR_G
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
The VSM data set is assigned to a VSM evaluation using this parameter.
Note:
If two VSM are connected at the Motor Module, then the first (p0151[0]) is assigned to the line voltage measurement
(see p3801) and the second, to the motor voltage measurement (see p1200).
p0154
DRIVE-CLiQ Hub Module detection via LED / Hub detection LED
HUB
Can be changed: U, T
Data type: Unsigned8
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Detects any DRIVE-CLiQ Hub Module that has been assigned.
p0154
Terminal Module detection via LED / TM detection LED
TM150, TM31,
Can be changed: U, T
TM54F_MA,
Data type: Unsigned8
TM54F_SL
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Detects the Terminal Module assigned to this drive and data set.
Note:
While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Terminal Module.
p0155[0...n]
Voltage Sensing Module activate/de-activate / VSM act/deact
VECTOR_G
Can be changed: C1(4), T
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/de-activate a Voltage Sensing Module (VSM).
Value:
0:
1:
2:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
De-activate component
Activate component
Component de-activate and not present
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: p0150
Units group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: p0150
Units group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1