Motor/Encoder Data Set Selected / Mds/Eds Selected; Motor Changeover Contactor Control Delay Time / Mot_Chg Ctrl T_Del; Bi: On / Off (Off1) / On / Off (Off1) - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Bit field:
Bit
00
01
02
03
04
Dependency:
Refer to: r0051, p0820, p0821, p0822, p0823, p0824
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
r0838[0...3]

Motor/Encoder Data Set selected / MDS/EDS selected

VECTOR_G
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the selected Motor Data Set (MDS) and the selected Encoder Data Sets (EDS).
Index:
[0] = Motor Data Set MDS selected
[1] = Encoder 1 Encoder Data Set EDS selected
[2] = Encoder 2 Encoder Data Set EDS selected
[3] = Encoder 3 Encoder Data Set EDS selected
Dependency:
Refer to: r0049, p0186, p0187, p0188, p0189
Note:
Value 99 means the following: No encoder assigned (not configured).
p0839

Motor changeover contactor control delay time / Mot_chg ctrl t_del

VECTOR_G
Can be changed: C2(3)
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for the contactor control for the motor changeover.
Note:
The delay time is taken into account in the following cases:
- for feedback signal, previous contactor "Open". The new motor contactor is controlled (energized) after the delay
time has expired.
- for the feedback signal, new motor contactor "Closed". The pulses are enabled after the delay time has expired.
p0840[0...n]

BI: ON / OFF (OFF1) / ON / OFF (OFF1)

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommend.:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p1055, p1056
Caution:
When "master control from PC" is activated, this binector input is ineffective.
256
Signal name
DDS select. bit 0
DDS select. bit 1
DDS select. bit 2
DDS select. bit 3
DDS select. bit 4
1 signal
ON
ON
ON
ON
ON
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
500 [ms]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
0 signal
OFF
OFF
OFF
OFF
OFF
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 3
Func. diagram: 2501, 2610,
8720, 8820, 8920
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150