p3112[0...n]

BI: External fault 3 enable negated / Ext flt 3 enab neg

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
p3112
BI: External fault 3 enable negated / Ext flt 3 enab neg
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN, ENC,
Not for motor type: -
HUB, TB30, TM150,
TM31, TM54F_MA,
Min
TM54F_SL
-
Description:
Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
r3113.0...15

CO/BO: NAMUR message bit bar / NAMUR bit bar

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the status of the NAMUR message bit bar.
The faults and alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
15
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Fault converter information
electronics/software error
Network fault
DC link overvoltage
Fault drive converter power electronics
Drive converter overtemperature
Ground fault
Motor overload
Bus error
External safety-relevant shutdown
Mot encoder fault
Error communication internal
Fault infeed
Other faults
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
-
-
-
-
-