Automatic Restart Start Attempts / Ar Start Attempts - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p1210
Automatic restart mode / AR mode
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the automatic restart mode (AR).
Value:
0:
1:
4:
6:
14:
16:
Recommend.:
For brief line supply failures, the motor shaft may still be rotating when restarting. The "flying restart" function (p1200)
might need to be activated to restart while the motor shaft is still rotating.
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Operator Panel in the LOCAL mode, then there is no automatic start.
For p1210 = 14, 16, a manual acknowledgement is required for an automatic restart.
Refer to: p0840, p0857, p1267
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is powered up
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic power-up sequence can only be interrupted by withdrawing the ON
command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). When faults
are present, therefore, the parameter cannot be changed.
For p1210 > 1, the motor is automatically started.
Note:
When automatic restart mode is activated, the supply voltage must remain connected (e.g. backed up by UPS).
Re p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledgment,
then these are also automatically acknowledged again. p1211 has no influence on the number of acknowledgment
attempts.
Re p1210 = 4:
An automatic restart is only carried out if fault F30003 occurred at the Motor Module or a 1 signal is present at
binector input p1208[1]. If additional faults are present, then these faults are also acknowledged and when
successful, starting continues. If the 24 V Control Unit power supply fails, then this is interpreted as a line supply
failure.
Re p1210 = 6:
An automatic restart is carried out if any fault has occurred or there is a 1 signal at binector input p1208[0].
Re p1210 = 14:
As for p1210 = 4. However, faults that are present must be manually acknowledged.
Re p1210 = 16:
As for p1210 = 6. However, faults that are present must be manually acknowledged.
p1211

Automatic restart start attempts / AR start attempts

B_INF
Can be changed: U, T
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the start attempts of the automatic restart function for p1210 = 4, 6.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Inhibit automatic restart
Acknowledge all faults without restarting
Restart after line supply failure w/o additional start attempts
Restart after fault with additional start attempts
Restart after line supply failure following man. acknowledgment
Restart after fault following manual acknowledgment
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
16
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3
317

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents