Si Tm54F Special Operating Mode Input Terminal / Si Spec Mode F-Di; Si Tm54F Agreement Input Terminal / Si Agreement F-Di - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
If value = 0:
No terminal assigned, selection bit remains statically at "0".
If value = 255:
No terminal assigned, selection bit remains statically at "1".
F-DI: Failsafe Digital Input
SLP: Safely-Limited Position
p10036[0...3]

SI TM54F special operating mode input terminal / SI spec mode F-DI

TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the input terminal for "special operating mode" (operating mode "function interface").
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
255:
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Note:
Parameter being prepared. For this firmware version, the function interface is not supported.
If value = 0:
No terminal assigned, static special operation.
If value = 255:
No terminal assigned, static normal operation.
p10037[0...3]

SI TM54F agreement input terminal / SI agreement F-DI

TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the input terminal for "agreement" (operating mode "function interface").
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
255:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Statically active
F-DI 0 (X521.2/3/6)
F-DI 1 (X521.4/5/7)
F-DI 2 (X522.1/2/7)
F-DI 3 (X522.3/4/8)
F-DI 4 (X522.5/6/9)
F-DI 5 (X531.2/3/6)
F-DI 6 (X531.4/5/7)
F-DI 7 (X532.1/2/7)
F-DI 8 (X532.3/4/8)
F-DI 9 (X532.5/6/9)
Statically inact
Statically active
F-DI 0 (X521.2/3/6)
F-DI 1 (X521.4/5/7)
F-DI 2 (X522.1/2/7)
F-DI 3 (X522.3/4/8)
F-DI 4 (X522.5/6/9)
F-DI 5 (X531.2/3/6)
F-DI 6 (X531.4/5/7)
F-DI 7 (X532.1/2/7)
F-DI 8 (X532.3/4/8)
F-DI 9 (X532.5/6/9)
Statically inact
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
981

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents