Tm150 Temperature Filter Time Constant / Tm150 Temp_Filt T; Tm150 Filter Rated Line Frequency / Tm150 Filt F_Line; Motor Temperature Sensor 1 Sensor Type / Temp_Sens 1 Type - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4120
r4120

TM150 temperature filter time constant / TM150 temp_filt T

TM150
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
- [ms]
Description:
Displays the smoothing time constant for the temperature filter for Terminal Module 150 (TM150).
Dependency:
Refer to: r4105, p4111, r4112, r4113
Note:
The time constant lies in the range from 80 to 1000 ms and depends on the number of channels that are
simultaneously active.
p4121

TM150 filter rated line frequency / TM150 filt f_line

TM150
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the rated line frequency for the filter to skip the line frequency for Terminal Module 150 (TM150).
Value:
0:
1:
p4600[0...n]

Motor temperature sensor 1 sensor type / Temp_sens 1 type

VECTOR_G
Can be changed: C2(3), U, T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the sensor type of the first temperature sensor for the motor temperature monitoring.
Value:
0:
10:
11:
12:
20:
30:
31:
32:
Dependency:
Refer to: r0458, p0600, p0601
Note:
This parameter is effective only when p0601 = 10.
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
636
50 Hz
60 Hz
No sensor
PTC fault
PTC alarm
PTC alarm & timer
KTY84
Bimetallic NC contact fault
Bimetallic NC contact alarm
Bimetallic NC contact alarm & timer
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
32
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130