Function Generator Period / Fg Period Duration; Function Generator Pulse Width / Fg Pulse Width; Function Generator Bandwidth / Fg Bandwidth; Function Generator Amplitude / Fg Amplitude - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p4821

Function generator period / FG period duration

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the period of the signal to be generated for the function generator.
Dependency:
Ineffective when p4820 = 4 (PRBS).
p4822

Function generator pulse width / FG pulse width

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the pulse width for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 1 (square-wave).
p4823

Function generator bandwidth / FG bandwidth

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
0.0025 [Hz]
Description:
Sets the bandwidth for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 4 (PRBS).
Refer to: p4830
p4824

Function generator amplitude / FG amplitude

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the amplitude for the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
p4825
Function generator 2nd amplitude / FG 2nd amplitude
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the second amplitude for the signal to be generated for the function generator.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
16000.0000 [Hz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1600.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1600.00 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
1000.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
500.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
4000.0000 [Hz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
5.00 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
7.00 [%]
679

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents