2 Parameters
2.2 List of parameters
Note:
Procedure:
1. In Index 0, enter which motor data set should be copied.
2. In Index 1, enter the motor data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0139[2] is automatically set to 0 when copying is completed.
When copying, p0131 is not taken into account.
p0140
Number of Encoder Data Sets (EDS) / EDS count
ENC
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
1
Description:
Sets the number of Encoder Data Sets (EDS).
Note:
When parameterizing the drive with "no encoder" there must be at least one encoder data set (p0140 >= 1).
p0140
Number of Encoder Data Sets (EDS) / EDS count
VECTOR_G
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
1
Description:
Sets the number of Encoder Data Sets (EDS).
Note:
When parameterizing the drive with "no encoder" there must be at least one encoder data set (p0140 >= 1).
p0141[0...n]
Encoder interface (Sensor Module) component number / Enc_interf comp_no
ENC, VECTOR_G
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
This parameter is used to assign the encoder data set to an encoder evaluation (e.g. SMC).
This unique component number is assigned when parameterizing the topology.
Only a component number can be entered that corresponds to an encoder evaluation.
Note:
If the encoder evaluation and encoder are integrated (motor with DRIVE-CLiQ), then their component numbers are
identical.
For an SMC, different component numbers are assigned for the SMC (p0141) and the (actual) encoder (p0142).
SMC: Sensor Module Cabinet
p0142[0...n]
Encoder component number / Encoder comp_no
ENC, VECTOR_G
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
This parameter is used to assign the encoder data set to an encoder.
This assignment is made using the unique component number that was assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to an encoder.
90
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
16
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
199
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 8570
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 8570
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 4704, 8570
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 4704
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150