Temperature Sensor, Sensor Type / Temp_Sens Type; Motor Temperature Sensor Type / Mot_Temp_Sens Type - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Re p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is
connected at the adapter (X210).
Re p0600 = 20, 21:
The BICO interconnection should be executed via connector input p0608 or p0609.
Associated parameters: p0601, p4600 ... p4603, p4610 ... p4613
p0601

Temperature sensor, sensor type / Temp_sens type

B_INF
Can be changed: C2(3), U, T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the sensor type for the temperature measurement at input X21 (booksize) or X41 (chassis).
The measured value is displayed in r0035.
Value:
0:
1:
2:
4:
Dependency:
Refer to: r0035
Note:
The measured value display depends on the selected sensor type.
Re p0601 = 0:
--> r0035 = -200 °C
Re p0601 = 1:
Tripping resistance = 1650 Ohm (lower resistance --> r0035 = -50 °C, higher resistance --> r0035 = 250 °C).
Re p0601 = 2:
Displays the temperature in °C.
Re p0601 = 4:
r0035 = -50 °C
--> The tripping resistance is less than 100 Ohm (bimetallic NC contact is closed or has a short-circuit).
r0035 = 250 °C
--> The tripping resistance is greater than 100 Ohm (bimetallic NC contact is open, not connected or has a wire
breakage).
When using the following components, a value of 4 is set as the factory setting and can no longer be changed:
- Basic Line Module (BLM) with internal Braking Module.
- Active Line Module (ALM) with line filter Active Interface Module (AIM, p0220[0] = 41 ... 45).
In these cases, in addition to the temperature display, the temperature is also monitored.
p0601[0...n]

Motor temperature sensor type / Mot_temp_sens type

VECTOR_G
Can be changed: C2(3), U, T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the sensor type for the motor temperature monitoring.
Value:
0:
1:
2:
3:
4:
5:
10:
11:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
No sensor
PTC alarm & timer
KTY84
Bimetallic NC contact alarm & timer
No sensor
PTC alarm & timer
KTY84
KTY84 and PTC (only for motors with DRIVE-CLiQ):
Bimetallic NC contact alarm & timer (only for temp_eval via MM)
PT100
Evaluation via several temperature channels SME12x
Evaluation via several temperature channels BICO
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
11
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
2
217

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents