Si Tm54F Failsafe Events Active / Si Failsafe Act; Si Tm54F Communication Status Drive-Specific / Si Comm_Stat Drv - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r10054

SI TM54F failsafe events active / SI failsafe act

TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the events that lead to the transfer of failsafe signals to all drives assigned to the TM54F. If the second
channel of the TM54F transmits failsafe signals, then these are synchronized to the other channel. In this particular
case, p10054 of the other TM54F channel should be evaluated.
Possibilities of resolving the situation:
- error during test stop: correctly perform the test stop.
- internal software error: no possibility of resolving this problem, POWER ON.
- internal synchronization problem: no possibility of resolving this problem, POWER ON.
- internal status error: no possibility of resolving this problem, POWER ON.
- parameterizing error: evaluate description of alarms F35004 or F35006. Resolve parameterizing error. POWER ON.
After updating the firmware of the TM54F it is possible that a power on is required.
- all other causes: remove the cause of the error and carry out a safe acknowledgment (p10006).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
31
r10055

SI TM54F communication status drive-specific / SI comm_stat drv

TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the communication status of the individual drives with the Terminal Module 54F (TM54F).
For r10055 = 0, the following applies:
All drives assigned in p10010 communicate with the TM54F.
Bit field:
Bit
00
01
02
03
04
05
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Commissioning mode active (p0010 = 95)
Checksum error of the safety parameters
Internal synchronization problem within
TM54F
Internal software error
Overvoltage in the TM54F
Undervoltage in the TM54F
Error at test stop
Error for crosswise data comparison within
TM54F
Overtemperature in the TM54F
Internal status error
Param error
Failsafe events active on another channel
Signal name
Communication between drive 1 and
TM54F
Communication between drive 2 and
TM54F
Communication between drive 3 and
TM54F
Communication between drive 4 and
TM54F
Communication between drive 5 and
TM54F
Communication between drive 6 and
TM54F
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Not configured
Not configured
Not configured
Not configured
Not configured
Not configured
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Configured
Configured
Configured
Configured
Configured
Configured
FP
2847
-
-
-
-
-
-
-
-
-
-
-
FP
-
-
-
-
-
-
991