2 Parameters
2.2 List of parameters
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
p1039[0...n]

BI: Motorized potentiometer inversion / MotP inv

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
p1040[0...n]

Motorized potentiometer starting value / Mop start value

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
powered up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
p1041[0...n]

BI: Motorized potentiometer manual/automatic / Mop manual/auto

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the setpoint
must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
p1042[0...n]

CI: Motorized potentiometer automatic setpoint / Mop auto setpoint

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
292
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.000 [rpm]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 3020
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3020
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 3
Func. diagram: 3020
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3020
Unit selection: -
Expert list: 1
Factory setting
0