Si Motion Brake Ramp Reference Value (Control Unit); Si Motion Brake Ramp Delay Time (Control Unit) /; Si Motion Brake Ramp Monitoring Time (Control Unit) - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
Refer to: p9561, p9563
Note:
In the extended sense, a bus failure should be seen here as a communication error in the control signals of the safety
functions (e.g. via PROFIsafe or TM54F).
The main use of the wait time is the ESR function (Extended Stop and Retract).
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9581
SI Motion brake ramp reference value (Control Unit) / SI Mtn ramp ref CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
600.0000 [mm/min]
Description:
Sets the reference value to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency:
Refer to: p9582, p9583
p9581
SI Motion brake ramp reference value (Control Unit) / SI Mtn ramp ref CU
VECTOR_G (Safety
Can be changed: C2(95)
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
600.0000 [rpm]
Description:
Sets the reference value to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency:
Refer to: p9582, p9583
p9582
SI Motion brake ramp delay time (Control Unit) / SI Mtn rp t_del CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
10.00 [ms]
Description:
Sets the delay time for monitoring the brake ramp.
Monitoring of the brake ramp starts once the delay time has elapsed.
Dependency:
Refer to: p9581, p9583
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
Internally, the set time is limited downwards to 2 safety monitoring clock cycles (2 * p9500/p9300).
p9583
SI Motion brake ramp monitoring time (Control Unit) / SI Mtn rp t_mon CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.50 [s]
Description:
Sets the monitoring time to define the brake ramp.
The rate of rise of the brake ramp depends upon p9581 (reference value) and p9583 (monitoring time).
Dependency:
Refer to: p9581, p9582
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
900
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
240000.0000 [mm/min]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
240000.0000 [rpm]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
99000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3600.00 [s]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1500.0000 [mm/min]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1500.0000 [rpm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
250.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.00 [s]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents