Co: Technology Controller Fixed Value 13 / Tec_Ctr Fix Val 13; Co: Technology Controller Fixed Value 14 / Tec_Ctr Fix Val 14; Co: Technology Controller Fixed Value 15 / Tec_Ctr Fix Val 15; Technology Controller Fixed Value Selection Method - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2213[0...n]

CO: Technology controller fixed value 13 / Tec_ctr fix val 13

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 13 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2214[0...n]

CO: Technology controller fixed value 14 / Tec_ctr fix val 14

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 14 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2215[0...n]

CO: Technology controller fixed value 15 / Tec_ctr fix val 15

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 15 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2216[0...n]
Technology controller fixed value selection method / Tec_ctr FixVal sel
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Integer16
P-Group: Technology
Not for motor type: -
Min
1
Description:
Sets the method to select the fixed setpoints.
Value:
1:
2:
p2220[0...n]
BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to select a fixed value of the technology controller.
530
Direct selection
Binary selection
Calculated: -
Dyn. index: DDS, p0180
Units group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 7950
Unit selection: p0595
Expert list: 1
Factory setting
130.00 [%]
Access level: 2
Func. diagram: 7950
Unit selection: p0595
Expert list: 1
Factory setting
140.00 [%]
Access level: 2
Func. diagram: 7950
Unit selection: p0595
Expert list: 1
Factory setting
150.00 [%]
Access level: 2
Func. diagram: 7950, 7951
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 3
Func. diagram: 7950, 7951
Unit selection: -
Expert list: 1
Factory setting
0