r0074

CO: Modulat_depth / Modulat_depth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the actual modulation depth.
Dependency:
Refer to: r0028
Note:
For space vector modulation, 100% corresponds to the maximum output voltage without overcontrol.
Values above 100 % indicate an overcontrol condition - values below 100% have no overcontrol.
The phase voltage (phase-to-phase, rms) is calculated as follows:(r0074 x r0070) / (sqrt(2) x 100 %).
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0075

CO: Current setpoint field-generating / Id_set

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Display and connector output for the field-generating current setpoint (Id_set).
Note:
This value is irrelevant for the U/f control mode.
r0076

CO: Current actual value field-generating / Id_act

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Display and connector output for the field-generating current actual voltage (Id_act).
Dependency:
Refer to: r0029
Note:
This value is irrelevant for the U/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
r0077

CO: Current setpoint torque-generating / Iq_set

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Display and connector output for the torque/force-generating current setpoint.
Note:
This value is irrelevant for the U/f control mode.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 5730, 6730,
6731, 6799, 8940, 8950
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 6700, 6714,
6725
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: 5700, 5714,
5730, 6700, 6714, 6799
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: 6700, 6710
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents