Fault Cases Counter / Fault Cases Qty; Profibus Baud Rate / Pb Baud Rate; Device Identification / Device Ident - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0952

Fault cases counter / Fault cases qty

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Number of fault situations that have occurred since the last reset.
Dependency:
The fault buffer is deleted (cleared) by setting p0952 to 0.
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
r0963

PROFIBUS baud rate / PB baud rate

CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Displays the corresponding value for the PROFIBUS baud rate.
Value:
0:
1:
2:
3:
4:
6:
7:
8:
9:
10:
11:
255:
r0964[0...6]

Device identification / Device ident

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the device identification.
Index:
[0] = Company (Siemens = 42)
[1] = Device type
[2] = Firmware version
[3] = Firmware date (year)
[4] = Firmware date (day/month)
[5] = Number of drive objects
[6] = Firmware patch/hot fix
Note:
Example:
r0964[0] = 42 --> SIEMENS
r0964[1] = device type, see below
r0964[2] = 403 --> first part of the firmware version V04.03 (for second part, refer to index 6)
r0964[3] = 2010 --> year 2010
r0964[4] = 1705 --> 17th of May
r0964[5] = 2 --> 2 drive objects
r0964[6] = 200 --> second part, firmware version (complete version: V04.03.02.00)
274
9.6 kbit/s
19.2 kbit/s
93.75 kbit/s
187.5 kbit/s
500 kbit/s
1.5 Mbit/s
3 Mbit/s
6 Mbit/s
12 Mbit/s
31.25 kbit/s
45.45 kbit/s
Unknown
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 6700, 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130