p1021[0...n]

BI: Fixed speed setpoint selection Bit 1 / n_set_fixed Bit 1

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1020, p1022, p1023, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
p1022[0...n]

BI: Fixed speed setpoint selection Bit 2 / n_set_fixed Bit 2

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1020, p1021, p1023, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
p1023[0...n]

BI: Fixed speed setpoint selection Bit 3 / n_set_fixed Bit 3

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
Refer to: p1020, p1021, p1022, r1197
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2505, 3010,
3011
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2505, 3010,
3011
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2505, 3010,
3011
Unit selection: -
Expert list: 1
Factory setting
0
289