Trace 1 Trigger Instant / Trace 1 T_Trigger; Trace Memory Location Free / Trace Mem Free; Function Generator Control / Fg Control - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r2114, r3102, r4719
Notice:
The accuracy of the trigger instant depends on the accuracy of the underlying basis time.
For clarification:
The trigger instant is calculated with a µs accuracy. If the underlying basis time is only available with ms accuracy,
then as a result of rounding effects, an inaccuracy of 1 ms can occur.
When referred to r4719, the trigger instant can therefore deviate somewhat.
Note:
If the time calculation of the drive can be synchronized with a higher-level control, then this time can be taken from
the actual UTC time (r3102 ). Otherwise, the time is based on the system runtime (r2114).
r4798[0...1]

Trace 1 trigger instant / Trace 1 t_trigger

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the instant in time for fulfilling the trigger condition for trace recorder 1.
The time comprises milliseconds (index 0) and days (index 1).
Index:
[0] = Milliseconds
[1] = Days
Dependency:
Refer to: r2114, r3102, r4719
Notice:
The accuracy of the trigger instant depends on the accuracy of the underlying basis time.
For clarification:
The trigger instant is calculated with a µs accuracy. If the underlying basis time is only available with ms accuracy,
then as a result of rounding effects, an inaccuracy of 1 ms can occur.
When referred to r4719, the trigger instant can therefore deviate somewhat.
Note:
If the time calculation of the drive can be synchronized with a higher-level control, then this time can be taken from
the actual UTC time (r3102 ). Otherwise, the time is based on the system runtime (r2114).
r4799

Trace memory location free / Trace mem free

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the free memory for the trace in bytes.
Dependency:
Refer to: r4708
p4800

Function generator control / FG control

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: Trace and function generator
CU_G150_PN
Not for motor type: -
Min
0
Description:
The function generator is started with p4800 = 1.
The signal is only generated for a 1 signal of binector input p4819.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p4819
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Stop function generator
Start function generator
Check function generator parameterization
Start function generator without enable signals
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0
675