Motor Holding Brake Braking Threshold Delay Exceeded; Brake Control Diagnostics Evaluation / Brake Diagnostics; Bi: Motor Holding Brake Or/And Logic Operation / Brake Or And - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p1277
Motor holding brake braking threshold delay exceeded / Del thresh exceed
VECTOR_G (Ext
Can be changed: U, T
brake)
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.000 [s]
Description:
Sets the delay time for the signal "braking threshold exceeded" (BO: r1229.6).
Dependency:
Refer to: p1220, p1221, r1229
p1278

Brake control diagnostics evaluation / Brake diagnostics

VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the brake control type (with or without diagnostics evaluation).
Example for brake control with diagnostics evaluation.
- brake control in the Motor Modules in booksize format
- Safe Brake Relay for AC Drive
Example for brake control without diagnostics evaluation.
- Brake Relay for AC Drive
Value:
0:
1:
Note:
If the configuration of the motor holding brake (p1215) is set to "no holding brake present" when booting, then an
automatic identification of the motor holding brake will be carried out. If a brake control is detected without
diagnostics evaluation (e.g. Brake Relay for AC Drive), then the parameter is set to "brake control without diagnostics
evaluation".
It is not permissible to parameterize "brake control without diagnostics evaluation" and also enable "safe brake
control" (p1278 = 1, p9602 = 1, p9802 = 1).
p1279[0...3]

BI: Motor holding brake OR/AND logic operation / Brake OR AND

VECTOR_G (Ext
Can be changed: T
brake)
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source for the OR/AND logic operation.
Dependency:
Refer to: r1229
Note:
[0]: OR logic operation, input 1 --> the result is displayed in r1229.10.
[1]: OR logic operation, input 2 --> the result is displayed in r1229.10.
[2]: AND logic operation, input 1 --> the result is displayed in r1229.11.
[3]: AND logic operation, input 2 --> the result is displayed in r1229.11.
342
Brake control with diagnostics evaluation
Brake control without diagnostics evaluation
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
300.000 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 2707
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2707
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150