Fault Drive Object Initiating / F Do Initiating; Bi: Acknowledgement Automatically Suppressed / Ackn Suppress; Change Safety Message Type / Ch. Si Mess Type; Component Fault / Comp Fault - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r3115[0...63]

Fault drive object initiating / F DO initiating

All objects
Can be changed: -
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
p3116

BI: Acknowledgement automatically suppressed / Ackn suppress

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN
Not for motor type: -
Min
-
Description:
Sets the signal source for the automatic acknowledgement on the device drive object.
BI: p3116 = 0 signal
Faults present are automatically acknowledged on the device drive object. Local device faults are forwarded to the
first active drive object.
BI: p3116 = 1 signal
Faults present are not automatically acknowledged on the device drive object. Local device faults are not forwarded.
Dependency:
Refer to: p2102, p2103, p2104, p2105, p3981
Note:
When selecting a standard telegram, the BICO interconnection for control signal STW1.10 (master control by PLC) is
automatically established.
p3117

Change safety message type / Ch. SI mess type

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Messages
CU_G150_PN
Not for motor type: -
Min
0
Description:
Sets the re-parameterization of all safety messages for faults and alarms.
The relevant message type during changeover is selected by the firmware.
0: Safety messages are not re-parameterized
1: Safety messages are re-parameterized
Note:
A change only becomes effective after a POWER ON.
r3120[0...63]

Component fault / Comp fault

All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the component of the fault which has occurred.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
-
557