Note:
For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with motor data set 0 and 1 (MDS).
p0652[0...n]

Motor stator resistance scaling / Mot R_stator scal

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
10.0 [%]
Description:
Sets the factor to evaluate the stator resistance.
Dependency:
Refer to: p0350, r0370
p0653[0...n]

Motor stator leakage inductance scaling / Mot L_S_leak scal

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
10.0 [%]
Description:
Sets the factor to evaluate the stator leakage induction.
Dependency:
Refer to: p0356, r0377
p0655[0...n]
Motor magnetizing inductance d axis saturated scaling / Mot L_m d sat scal
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
10.0 [%]
Description:
Factor to evaluate the magnetizing inductance in the direction of the rotor axis (d axis).
Dependency:
Refer to: p0360, r0382
p0656[0...n]
Motor magnetizing inductance q axis saturated scaling / Mot L_m q sat scal
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
10.0 [%]
Description:
Factor to evaluate the magnetizing inductance quadrature to the rotor axis (q axis).
Dependency:
Refer to: p0361, r0383
p0657[0...n]

Motor damping inductance d axis scaling / Mot L_damp d scal

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PEM, REL
Min
10.0 [%]
Description:
Factor to evaluate the damping inductance in the direction of the rotor axis (d axis).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
300.0 [%]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
300.0 [%]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
300.0 [%]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
300.0 [%]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
300.0 [%]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: 6727
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]