Dependency:
"Quick commissioning" must be carried out (p0010 = 1) before executing the motor data identification routine!
In the simulation mode, the parameter cannot be written into. When selecting the motor data identification routine, the
drive data set changeover is suppressed.
Refer to: p1272, p1900
Notice:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next power-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Note:
If there is a motor holding brake, it must be open (p1215 = 2).
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971, p0977).
When setting p1910, the following should be observed:
1. "With acceptance" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influence
on the controller setting.
2. "Without acceptance" means:
The identified parameters are only displayed in the range r1912 ... r1926. The controller settings remain unchanged.
3. p1910 = 3, 4, 5 can only be selected for induction motors.
4. For settings 27 and 28, the AVC configuration set using p1840 is active.
The power-on command must remain set during a measurement and after the measurement has been completed,
the drive automatically resets it. The duration of the measurements can lie between 0.3 s and several minutes. This
time is mainly influenced by the motor size. At the end of the motor data identification, p1910 is automatically set to 0,
if only the stationary measurement is selected, then p1900 is also reset to 0, otherwise, the rotating measurement is
activated.
p1911
Phases to be identified number / Ph to ident qty
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Motor identification
Not for motor type: -
Min
1
Description:
Sets the number of phases to be identified.
Value:
1:
2:
3:
Note:
When identifying with several phases, the accuracy increases and also the time it takes to make the measurement.
r1912[0...2]
Identified stator resistance / R_stator ident
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor identification
Not for motor type: -
Min
- [ohm]
Description:
Displays the identified stator resistance.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
Enter voltage vector with DTC correction
Enter voltage vector with AVC
Enter voltage vector with DTC + AVC correction
1 phase U
2 phases U, V
3 phases U, V, W
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ohm]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
445