p3233[0...n]

Torque actual value filter time constant / M_act_filt T

VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and signals.
p3235

Phase failure signal motor monitoring time / Ph_fail t_monit

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time for phase failure detection of the motor.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Monitoring is only effective for blocksize and booksize power units.
For p3235 = 0 the function is deactivated.
For VECTOR, the following applies:
The monitoring is automatically de-activated during the flying restart operation for a motor that is still rotating.
p3236[0...n]

Speed threshold 7 / n_thresh val 7

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: REL
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "speed deviation model/external" (BO: r2199.7).
Dependency:
Refer to: r1443, r2169, r2199, p3237
p3237[0...n]

Hysteresis speed 7 / n_hysteresis 7

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the hysteresis speed for the signal "speed deviation model/external" (BO: r2199.7).
Dependency:
Refer to: r2199, p3236
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1000000 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2000 [ms]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
3000.00 [rpm]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
200.00 [rpm]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8013
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
320 [ms]
Access level: 3
Func. diagram: 8012
Unit selection: p0505
Expert list: 1
Factory setting
100.00 [rpm]
Access level: 3
Func. diagram: 8012
Unit selection: p0505
Expert list: 1
Factory setting
2.00 [rpm]