2 Parameters
2.2 List of parameters
p1523[0...n]

CI: Torque limit lower / M_max lower

VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the lower torque limit.
Dependency:
Refer to: p1520, p1521, p1522
Danger:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
p1524[0...n]

CO: Torque limit upper scaling / M_max upper scal

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-2000.0 [%]
Description:
Sets the scaling for the upper torque limit.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
p1525[0...n]

CO: Torque limit lower scaling / M_max lower scal

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-2000.0 [%]
Description:
Sets the scaling for the lower torque limit.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
r1526

CO: Torque limit upper without offset / M_max up w/o offs

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Nm]
Description:
Display and connector output for the upper torque limit of all torque limits without offset.
Dependency:
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
382
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2003
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: PERCENT
Max
2000.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: PERCENT
Max
2000.0 [%]
Calculated: -
Dyn. index: -
Units group: 7_1
Scaling: p2003
Max
- [Nm]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 6020, 6630
Unit selection: -
Expert list: 1
Factory setting
1521[0]
Access level: 3
Func. diagram: 6630
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 3
Func. diagram: 6630
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 3
Func. diagram: 6060, 6630,
6640
Unit selection: p0505
Expert list: 1
Factory setting
- [Nm]