p0329[0...n]

Motor pole position identification current / Mot PolID current

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, REL, FEM
Min
0.00 [Arms]
Description:
Sets the current for the pole position identification routine (p1980 = 1).
For a two-stage technique (p1980 = 4) , the current is set for the 2nd phase.
The current for the 1st phase is set in p0325.
Dependency:
The following applies for vector drives:
If a maximum current (p0323) was not parameterized, then p0329 is limited to the rated motor current.
Refer to: p0325, p1980, p1982, r1984, r1985, r1987, p1990
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
r0330[0...n]
Rated motor slip / Mot slip_rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
- [Hz]
Description:
Displays the rated motor slip.
Dependency:
The rated slip is calculated from the rated frequency, rated speed and number of pole pairs.
Refer to: p0310, p0311, r0313
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
r0331[0...n]
Actual motor magnetizing current/short-circuit current / Mot I_mag_rtd act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, FEM
Min
- [Arms]
Description:
Induction motor:
Displays the rated magnetizing current from p0320.
For p0320 = 0, the internally calculated magnetizing current is displayed.
Synchronous motor:
Displays the rated short-circuit current from p0320.
Dependency:
If p0320 was not entered, then the parameter is calculated from the rating plate parameters.
Note:
In the case of multi-motor operation r0331 is increased by the factor p0306 compared to p0320.
r0332[0...n]
Rated motor power factor / Mot cos phi rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL
Min
-
Description:
Displays the rated power factor for induction motors.
128
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
10000.00 [Arms]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
- [Hz]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
- [Arms]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 3
Func. diagram: 5722, 6722,
6724
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1