Can Pre-Defined Error Field / Pre_Def Err Field - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
Corresponds to the CANopen object 1200 hex.
SDO: Service Data Object
p8611[0...82]

CAN Pre-defined Error Field / Pre_def err field

CU_G130_DP (CAN),
Can be changed: U, T
CU_G130_PN (CAN),
Data type: Unsigned32
CU_G150_DP (CAN),
P-Group: -
CU_G150_PN (CAN)
Not for motor type: -
Min
0000 hex
Description:
Displays the Pre-defined Error Field of the CAN node.
It includes the number of all errors that have occurred, the number of errors that have occurred for each drive and the
errors according to their history.
The first 16 bits represent the CANopen error code and the second 16 bits the SINAMICS error code.
Index 1 has the same structure - however, the drive object ID is in the second 16 bits instead of the SINAMICS error
code.
CANopen error code:
0000 hex: No error present.
8110 hex: Alarm A08751 present.
8120 hex: Alarm A08752 present.
8130 hex: Alarm A08700(F) with alarm value = 2 present.
1000 hex: Generic error 1 present (there is at least one fault outside the range 8700 ... 8799)
1001 hex: Generic error 2 present (there is at least one alarm in the range 8700 ... 8799 with the exception of
A08751, A08752, A08700)
All drive objects are acknowledged by writing the value 0 to index 0. As soon as a fault has been acknowledged or an
alarm cleared, then it is also cleared from the fault list.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
FFFF 1000 hex
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex