r9781[0...1]

SI checksum to check changes (Control Unit) / SI chg chksm CU

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Safety Integrated
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the checksum for tracking changes for Safety Integrated.
These are additional checksums that are created to track changes (fingerprint for the "safety logbook" functionality) to
safety parameters (that are relevant for checksums).
Index:
[0] = SI checksum to track functional changes
[1] = SI checksum to track hardware-specific changes
Dependency:
Refer to: p9601, p9729, p9799
r9782[0...1]

SI time stamps to check changes (Control Unit) / SI chg t CU

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Safety Integrated
CU_G150_PN
Not for motor type: -
Min
- [h]
Description:
Displays the time stamps for the checksums for tracking changes for Safety Integrated.
The time stamps for the checksums for tracking changes (fingerprint for the "safety logbook" functionality) made to
safety parameters are saved in parameters p9781[0] and p9781[1].
Index:
[0] = SI time stamp for checksum to track functional changes
[1] = SI time stamp for checksum to track hardware-specific changes
Dependency:
Refer to: p9601, p9729, p9799
p9783
SI Motion act. value sensing sensorless synchr. motor I_inject / Actv sl sync I_inj
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-50.00 [%]
Description:
Sets the additional field-generating current for synchronous motors with sensorless actual value sensing.
The set value is referred to p0305.
This parameter ensures a "base load" for the motor.
The value must fulfill the following condition:
|p0305 x p9783| >= p9588 x 1.2
Dependency:
Refer to: p9588
Notice:
Reducing this percentage value can adversely affect actual value sensing with synchronous motors.
If the value is increased, this results in an increased motor power loss.
Note:
This parameter is only effective for encoderless actual value sensing (p9506/p9306 = 1, 3).
For p9783 = maximum value, current injection is deactivated.
Current injection is not effective in the U/f control mode.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [h]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
0.00 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [h]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-20.00 [%]