Co/Bo: Si Tm54F Digital Outputs Status / Si Do Status; Co/Bo: Si Tm54F Digital Inputs 20 ... 23 Status / Si Di 20...23 Stat - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
07
08
09
Dependency:
Refer to: p10017, p10040
Note:
If a safety function is assigned to an input (e.g. via p10022), then the following applies:
- logical "0": Safety function is selected
- logical "1": Safety function is de-selected
The interrelationship between the logical level and the external voltage level at the input depends on the
parameterization (refer to p10040) of the input as either NC or NO contact and is aligned to the use of a safety
function:
With 24 V at the input, NC contacts have a logical "1" level, for 0 V at the input, a logical "0" level.
This means that an NC/NC contact parameterization of 0 V at both inputs of the F-DI selects the safety function, for
24 V at both inputs, de-selects the safety function.
With 24 V at the input, NO contacts have a logical "0" level, for 0 V at the input, a logical "1" level.
This means that for an NC/NO contact parameterization, the level 0 V/24 V selects the safety function, the level 24
V/0 V de-selects the safety function.
F-DI: Failsafe Digital Input
r10052.0...3

CO/BO: SI TM54F digital outputs status / SI DO status

TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the status of the digital outputs at the Terminal Module 54F (TM54F).
TM54F_MA (master): display of DO-
TM54F_SL (slave): display of DO+
Bit field:
Bit
00
01
02
03
Note:
F-DO: Failsafe Digital Output
r10053.0...3

CO/BO: SI TM54F digital inputs 20 ... 23 status / SI DI 20...23 stat

TM54F_SL
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the status of the digital inputs at the Terminal Module 54F (TM54F).
Bit field:
Bit
00
01
02
03
990
F-DI 7
F-DI 8
F-DI 9
Signal name
DO 0
DO 1
DO 2
DO 3
Signal name
DI 20
DI 21
DI 22
DI 23
Logical 1
Logical 1
Logical 1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
High
High
High
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
High
High
High
List Manual (LH2), 04/2014, A5E03263479A
Logical 0
Logical 0
Logical 0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Access level: 3
Func. diagram: 2848
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low