p0626[0...n]

Motor overtemperature, stator core / Mot T_over core

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
10 [K]
Description:
Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency:
For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0627[0...n]

Motor overtemperature, stator winding / Mot T_over stator

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
15 [K]
Description:
Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency:
For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0628[0...n]

Motor overtemperature rotor winding / Mot T_over rotor

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
20 [K]
Description:
Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency:
For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice:
When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
226
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: 21_2
Scaling: -
Max
200 [K]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: 21_2
Scaling: -
Max
200 [K]
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: 21_2
Scaling: -
Max
200 [K]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
50 [K]
Access level: 3
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
80 [K]
Access level: 3
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
100 [K]