Co: Speed Setpoint After The Filter / N_Set After Filter; Co: Speed Actual Value / N_Act; Co: Speed Controller System Deviation / N_Ctrl System Dev - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
With a parameterized filter time constant p1441, the speed signal from encoder 1 is displayed corrected by the
following error.
The speeds from encoder 2 and 3 are only displayed in U/f operating modes if the function module (speed/torque
control) (r0108.2) has been activated.
r0062

CO: Speed setpoint after the filter / n_set after filter

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [rpm]
Description:
Display and connector output for the speed setpoint after the setpoint filters.
r0063[0...2]

CO: Speed actual value / n_act

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [rpm]
Description:
Displays the actual speed of the closed-loop speed control and the U/f control.
For U/f control and when slip compensation is deactivated (see p1335), the synchronous speed to the output
frequency is shown in r0063[0].
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Calculated from f_set - f_slip
Dependency:
Refer to: r0021, r0022
Note:
The speed actual value is calculated in encoderless operation and for U/f control.
For operation with encoder, r0063[0] is smoothed with p1441.
The speed actual value (r0063[0]) is additionally displayed - smoothed with p0045 - in r0063[1].
The speed (r0063[2]) calculated from the output frequency and slip can only be compared with the speed actual
value (r0063[0]) in the steady-state.
The actual speed (r0063[0]) is available as a display quantity with additional smoothing in r0021.
r0064

CO: Speed controller system deviation / n_ctrl system dev

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [rpm]
Description:
Displays the actual system deviation of the speed controller.
Note:
In servo control mode with active reference model, the system deviation to the P component of the speed controller is
displayed.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6020, 6030,
6031
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 4702, 4715,
6799
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 5040, 6040
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]