2 Parameters
2.2 List of parameters
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
r0207[0...4]
Rated power unit current / PU PI_rated
B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
r0208
Rated power unit line supply voltage / PU U_rated
B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400 : 380 - 480 V +/-10 %
r0208 = 500 : 500 - 600 V +/-10 %
r0208 = 690 : 660 - 690 V +/-10 %
For the Basic Line Module (BLM) the following applies:
r0208 = 690 : 500 - 690 V +/-10 %
r0209[0...4]
Power unit maximum current / PU I_max
B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
104
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [Vrms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [Arms]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 8014
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 2
Func. diagram: 8750, 8850,
8950
Unit selection: -
Expert list: 1
Factory setting
- [Arms]