2 Parameters
2.2 List of parameters
r0030

Current actual value torque-generating smoothed / Iq_act smooth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
Note:
SERVO: Smoothing time constant = 100 ms
VECTOR: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The following applies for SERVO:
The torque-generating current actual value is available smoothed (r0030 with 100 ms, r0078[1] with p0045) and
unsmoothed (r0078[0]).
The following applies for VECTOR:
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
r0031

Actual torque smoothed / M_act smooth

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Nm]
Description:
Displays the smoothed torque actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque actual value is available smoothed (r0031) and unsmoothed (r0080).
r0032

CO: Active power actual value smoothed / P_actv_act smth

B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kW]
Description:
Displays the smoothed actual value of the active power.
Dependency:
Refer to: r0082
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
Significance for the drive: Power output at the motor shaft
Significance for the infeed: Line power drawn
For A_INF, B_INF and S_INF the following applies:
The active power is available smoothed (r0032 with 300 ms) and unsmoothed (r0082).
The following applies for SERVO:
The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]).
For VECTOR and VECTORMV, the following applies:
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
50
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: 7_1
Scaling: p2003
Max
- [Nm]
Calculated: -
Dyn. index: -
Units group: 14_10
Scaling: r2004
Max
- [kW]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 5730, 6799
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 2
Func. diagram: 5730, 6799
Unit selection: p0505
Expert list: 1
Factory setting
- [Nm]
Access level: 2
Func. diagram: 5730, 6799,
8750, 8850, 8950
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
SINAMICS G130/G150