2 Parameters
2.2 List of parameters
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700, p1000 and
p1500 are re-established and all of the dependent motor, open-loop and control-loop control parameters are
calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700, p1000 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
1:
2:
3:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motors p0320, p0352, p0353, p0362 ... p0369, p0391 ... p0393, p0604, p0605, p0626 ... p0628
synchronous motor p0326, p0327, p0352, p0353, p0391 ... p0393, p0604, p0605.
p3901[0...n]

Power unit EEPROM Vdc offset calibration / PU EEPROM Vdc offs

B_INF, VECTOR_G
Can be changed: C1, C2(1), T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-40.0 [V]
Description:
Differential voltage for calibrating the offset for DC-link voltage measurement.
Dependency:
Refer to: r0192, p0212
Caution:
Incorrect use of the calibration can have a negative impact on the closed-loop control.
The parameter influences the upper and lower voltage detection.
Note:
Parameter entries are directly saved in the DRIVE-CLiQ component involved.
The parameter is only effective in the case of booksize power units, if r0192.22 = 1 and p0212.0 = 1.
r3925[0...n]

Identification final display / Ident final_disp

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Displays the commissioning steps that have been carried out.
Bit field:
Bit
00
02
03
04
08
594
No quick parameterization
Quick parameterization after parameter reset
Quick parameterization (only) for BICO and motor parameters
Quick parameterization for motor parameters (only)
Signal name
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Motor data identification carried out at
standstill (p1910 = 1)
Rotating measurement carried out (p1960 =
1, 2)
Motor encoder adjustment carried out
(p1960 = 1, p1990 = 1, 3)
Motor identification data have been
automatically backed up
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
40.0 [V]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
SINAMICS G130/G150