1 signal:
The connected temperature sensor (X21.1, X21.2) signals an overtemperature. The highest permissible temperature
at the connected temperature sensor has been exceeded and results in a shutdown.
r3689

BO: Digital Braking Module Uce fault / Dig BM Uce fault

B_INF
Can be changed: -
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays an Uce fault in the internal Braking Module.
1 signal:
An Uce fault is present in the internal Braking Module.
p3800[0...n]

Sync-line-drive activation / Sync act

VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the activation for the line-drive synchronization.
Value:
0:
1:
Dependency:
Refer to: p3801, p3802
Caution:
If there is only one VSM being used, this can either be used for line synchronization or for a flying restart. If the VSM
was connected to the line supply, then flying restart should be deselected in p1200. If the VSM was connected at the
output (motor side), then line synchronization should be deactivated using p3800.
Line synchronization (first VSM connected with the line supply) and also flying restart (second VSM connected to the
motor terminals) can only be used if two VSMs are assigned to the Motor Module.
Note:
When the ground fault monitoring initiates a fault for overlapping synchronizing the threshold value p0287[1] for the
Motor Module and the associated infeed must be appropriately increased (e.g. p0287[1] = 100 %).
For p3800 = 1, the following applies:
The INTERNAL voltage actual values are used for synchronization. The effects that a (sine-wave) filter - that is
connected between the Motor Module and motor - has on the voltage actual values are taken into account
(theoretically) by appropriately selecting p0230.
VSM: Voltage Sensing Module
p3801[0...n]

Sync-line-drive drive object number / Sync DO_no

VECTOR_G
Can be changed: T
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
1
Description:
Sets the drive object number of the VSM used for the line-drive synchronization.
Dependency:
Refer to: p3800, p3802
Notice:
The current controller sampling time p0115[0] of the drive object with the VSM used for synchronization must be
identical to the current controller sampling time of the drive of the drive used to perform line synchronization.
Note:
VSM: Voltage Sensing Module
The setting p3801 = 1 is always possible (no VSM selected).
If the VSM is assigned subsequently to a Motor Module, its drive object number must be entered in p3801.
The line voltage is always measured using the first VSM (p0151[0]).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Sync-line-drive de-activated
Sync-line-drive activated VSM-INT
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
62
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
1