2 Parameters
2.2 List of parameters
Bit 27 = 1 (enable signal missing), if:
- de-magnetizing has still not been completed (only for vector).
Bit 28 = 1 (enable signal missing), if:
- the holding brake is closed or has still not been opened.
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
Bit 30 = 1 (speed controller inhibited), if one of the following reasons is present:
- A 0 signal is available via binector input p0856.
- the function generator with current input is active.
- the measuring function "current controller reference frequency characteristic" is active.
- the pole position identification is active.
- motor data identification is active (only certain steps).
Bit 31 = 1 (enable signal missing), if:
- the speed setpoint from jog 1 or 2 is entered.
r0047
Motor data identification and speed controller optimization / MotID and n_opt
VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Displays, signals
Not for motor type: -
Min
0
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity controller
optimization (rotating measurement).
Value:
0:
115:
120:
140:
150:
170:
190:
195:
200:
210:
220:
230:
240:
250:
270:
290:
300:
Note:
Re r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
r0049[0...3]
Motor data set/encoder data set effective / MDS/EDS effective
VECTOR_G
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the effective Motor Data Set (MDS) and the effective Encoder Data Sets (EDS).
Index:
[0] = Motor Data Set MDS effective
[1] = Encoder 1 Encoder Data Set EDS effective
[2] = Encoder 2 Encoder Data Set EDS effective
[3] = Encoder 3 Encoder Data Set EDS effective
Dependency:
Refer to: p0186, p0187, p0188, p0189, r0838
58
No measurement
Measurement q leakage inductance (part 2)
Speed controller optimization (vibration test)
Calculate speed controller setting
Measurement moment of inertia
Measurement magnetizing current and saturation characteristic
Speed encoder test
Measurement q leakage inductance (part 1)
Rotating measurement selected
Pole position identification selected
identification leakage inductance
Identification rotor time constant
Identification stator inductance
Identification stator inductance LQLD
Identification stator resistance
Identification valve lockout time
Stationary measurement selected
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
300
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150