Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Note:
For a general 2nd-order filter, by inserting the same natural frequency in both the numerator and in the denominator,
i.e. bandstop frequency, a bandstop filter is implemented. If the numerator damping of zero is selected, the bandstop
frequency is completely suppressed.
The denominator damping can be determined from the equation for the 3 dB bandwidth:
f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
p1663[0...n]
Current setpoint filter 2 denominator natural frequency / I_set_filt 2 fn_d
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.5 [Hz]
Description:
Sets the denominator natural frequency for current setpoint filter 2 (PT2, general filter).
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1664[0...n]
Current setpoint filter 2 denominator damping / I_set_filt 2 D_d
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.001
Description:
Sets the denominator damping for current setpoint filter 2.
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1665[0...n]
Current setpoint filter 2 numerator natural frequency / I_set_filt 2 fn_n
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.5 [Hz]
Description:
Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1666[0...n]
Current setpoint filter 2 numerator damping / I_set_filt 2 D_n
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.000
Description:
Sets the numerator damping for current setpoint filter 2.
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
16000.0 [Hz]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.000
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
16000.0 [Hz]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.000
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
1999.0 [Hz]
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
0.700
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
1999.0 [Hz]
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
0.700
409