2 Parameters
2.2 List of parameters
Dependency:
Refer to: p4652, r4653, r4654
Note:
The reset of XIST1_ERW depends on the selected mode (p4652).
p4660

Sensor Module filter bandwidth / SM Filt_bandw

ENC
Can be changed: C2(4)
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
0.00 [kHz]
Description:
Sets the filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The value set on the Sensor Module is displayed in r4661.
The Sensor Module hardware only supports the following values:
- 0: The Sensor Module's default is used.
- 50 kHz
- 170 kHz
- 500 kHz
- Unlimited: Only the bandwidth of the operational amplifier is effective.
Dependency:
Refer to: r4661
Note:
A value of zero is displayed if an encoder is not present.
p4660[0...2]
Sensor Module filter bandwidth / SM Filt_bandw
VECTOR_G
Can be changed: C2(4)
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
0.00 [kHz]
Description:
Sets the filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The value set on the Sensor Module is displayed in r4661.
The Sensor Module hardware only supports the following values:
- 0: The Sensor Module's default is used.
- 50 kHz
- 170 kHz
- 500 kHz
- Unlimited: Only the bandwidth of the operational amplifier is effective.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: r4661
Note:
A value of zero is displayed if an encoder is not present.
r4661

Sensor Module filter bandwidth display / SM Filt_bandw disp

ENC
Can be changed: -
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
- [kHz]
Description:
Display of the effective filter bandwidth for Sensor Module SMx10 (resolver) and SMx20 (sin/cos).
The bandwidth of the filter is set using p4660.
Dependency:
Refer to: p4660
Note:
A value of zero is displayed if an encoder is not present.
644
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
20000.00 [kHz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
20000.00 [kHz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [kHz]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [kHz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [kHz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [kHz]