p1212

Automatic restart delay time start attempts / AR t_wait start

B_INF
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.1 [s]
Description:
Sets the delay time up to restart.
Dependency:
This parameter setting is active for p1210 = 4, 6.
For p1210 = 1, the following applies:
Only automatic acknowledgment of the faults, no restart.
Refer to: p1210, r1214
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The faults are automatically acknowledged and the system is powered up again after half of the delay time has
expired and after the full delay time has expired.
p1212
Automatic restart delay time start attempts / AR t_wait start
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.1 [s]
Description:
Sets the delay time up to restart.
Dependency:
This parameter setting is active for p1210 = 4, 6.
For p1210 = 1, the following applies:
Faults are only automatically acknowledged in half of the waiting time, no restart.
Refer to: p1210, r1214
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The faults are automatically acknowledged after half of the delay time has expired and the full delay time.
If the cause of a fault is not removed in the first half of the delay time, then it is no longer possible to acknowledge in
the delay time.
p1213[0...1]

Automatic restart monitoring time / AR t_monit

B_INF
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Index:
[0] = Restart
[1] = Reset start counter
Dependency:
Refer to: p1210, r1214
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note:
Re index 0:
The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If the drive has not restarted at the end of the monitoring time, fault F07320 is signaled.
The monitoring is de-activated with p1213 = 0. If p1213 is set to a value which is lower than in p1212, fault F07320 is
generated at each restart. If, for p1210 = 1, the time in p1213 is set lower than in p1212, then fault F07320 is also
generated at each restart.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000.0 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000.0 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10000.0 [s]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [s]
319