p9549
SI Motion slip velocity tolerance (Control Unit) / SI Mtn slip tol
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [mm/min]
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitoring
channels.
Dependency:
Refer to: p9501, p9542
Note:
If the "actual value synchronization" is not enabled (p9501.3 = 0), then the value parameterized in p9542 is used as
tolerance in the crosswise data comparison.
p9549
SI Motion slip velocity tolerance (Control Unit) / SI Mtn slip tol
VECTOR_G (Safety
Can be changed: C2(95)
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the velocity tolerance that is used for a 2-encoder system in crosswise comparison between the two monitoring
channels.
Dependency:
Refer to: p9501, p9542
Note:
If the "actual value synchronization" is not enabled (p9501.3 = 0), then the value parameterized in p9542 is used as
tolerance in the crosswise data comparison.
p9550
SI Motion SGE changeover tolerance time (Control Unit) / SI Mtn SGE_chg tol
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the tolerance time for the changeover of the safety-related inputs (SGE).
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
p9551
SI Motion SLS(SG) changeover/SOS (SBH) delay time (CU) / SI SLS/SOS t CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the delay time for the SLS changeover and for the activation of SOS for the functions "Safely-Limited Speed"
(SLS) and "Safe operating stop" (SOS).
When transitioning from a higher to a lower safely-limited speed level, and when activating safe operating stop
(SOS), within this delay time, the "old" speed level remains active.
This delay is also applicable when activating SLS from the state "SOS and SLS inactive" and activating SOS from the
state "SOS inactive".
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SLS: Safely-Limited Speed / SG: Safely reduced speed
SOS: Safe Operating Stop / SBH: Safe operating stop
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
6000.00 [mm/min]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
6000.00 [rpm]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.00 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.00 [mm/min]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.00 [rpm]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
500.00 [ms]
Access level: 3
Func. diagram: 2819, 2820
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
891