p0040

Reset energy consumption display / Energy usage reset

VECTOR_G
Can be changed: U, T
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
0
Description:
Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency:
Refer to: r0039
r0041

Energy consumption saved / Energy cons saved

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kWh]
Description:
Displays the saved energy referred to 100 operating hours.
Dependency:
Refer to: p0040
Note:
This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
p0045

Display values smoothing time constant / Disp_val T_smooth

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the smoothing time constant for the following display values:
SERVO: r0078[1], r0079[1], r0081 (calculated from the quantities smoothed with p0045), r0082[1].
VECTOR: r0063[1], r0068[1], r0080[1], r0082[1].
r0046.0...29

CO/BO: Missing enable sig / Missing enable sig

B_INF
Can be changed: -
Data type: Unsigned32
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop infeed control from being
commissioned.
Bit field:
Bit
00
01
08
16
17
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
OFF1 enable missing
OFF2 enable missing
EP terminals enable missing
OFF1 enable internal missing
OFF2 enable internal missing
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [kWh]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
10000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [kWh]
Access level: 2
Func. diagram: 4715, 5610,
5730, 6714, 8012
Unit selection: -
Expert list: 1
Factory setting
1.00 [ms]
Access level: 1
Func. diagram: 8734
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
FP
-
-
-
-
-
55