List Of Parameters; Infeed Operating Display / Inf Op_Display; Control Unit Operating Display / Cu Op_Display - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2.2

List of parameters

Product: SINAMICS G130/G150, Version: 4702900, Language: eng
Objects: B_INF, CU_G130_DP, CU_G130_PN, CU_G150_DP, CU_G150_PN, ENC, HUB, TB30, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
r0002

Infeed operating display / INF op_display

B_INF
Can be changed: -
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Operating display for the infeed.
Value:
0:
31:
32:
35:
41:
42:
44:
45:
46:
60:
70:
200:
250:
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
COMM: Commissioning
r0002

Control Unit operating display / CU op_display

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Operating display for the Control Unit (CU).
Value:
0:
10:
20:
25:
31:
33:
34:
35:
70:
80:
99:
101:
111:
112:
113:
114:
115:
117:
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Operation - everything enabled
Rdy for sw on - pre-chrg running (p0857)
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
Switching on inhibited - carry out first commissioning (p0010)
Switching on inhibited - set "ON/OFF1" = "0" (p0840)
Switching on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
Switching on inhibited - connect 24 V to terminal EP (hardware)
Switching on inhibited - remove fault cause, acknowledge fault
Switching on inhibited - exit comm mode (p0009, p0010)
Infeed de-activated/not operational
Initialization
Wait for booting/partial booting
Device signals a topology error
Operation
Ready
Wait for run-up
Wait for automatic FW update of DRIVE-CLiQ components
Commissioning software download active
Remove/acknowledge topology error
Exit commissioning mode
Carry out first commissioning
Initialization
Reset active
Internal software error
Specify topology
Insert drive object
Delete drive object
Change drive object number
Change component number
Run parameter download
Delete component
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
250
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
117
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
33