AL019 Serial communication error
Trigger condition
and cause
Checking method
and corrective action
How to clear the
alarm?
AL020 Serial communication timeout
Trigger condition
and cause
Checking method
and corrective action
How to clear the
alarm?
AL022 RST leak phase
Trigger condition
and cause
Checking method
and corrective action
How to clear the
alarm?
Condition: RS-485 communication error.
Cause:
Improper setting of the communication parameters.
1.
Incorrect communication address.
2.
Incorrect communication value.
3.
1. Check the values of the communication parameters. Then correctly set P3.003
and P3.004 or restore the value to default.
Check and correctly set the communication address.
2.
Check and correctly set the accessing value.
3.
DI.ARST
Condition: RS-485 communication error.
Cause:
Improper setting of the timeout parameter (P5.003).
1.
Servo drive has not received the communication command for a long time and
2.
has timed out (refer to P5.003).
Check and make sure the value for the communication timeout parameter is
1.
correct.
Check if the communication cable is loose or broken and is correctly wired.
2.
DI.ARST
Condition: RST power cable is loose or there is no power. The default setting of
AL022 is a warning. To set AL022 as an alarm, you can set P2.066 [Bit 12].
Cause: RST leak phase.
Check if the RST power cable is loose or there is no power. This alarm occurs when
the 1.5 kW (or below) ASDA-A3 servo drive is not connected to the three-phase
power supply. For 2 kW (or above) ASDA-A3 servo drives, the alarm occurs when
one single phase is not connected to the power supply. Correctly connect the power
to the servo drive. If the issue persists, send your ASDA-A3 servo drive back to the
distributor or contact Delta.
DI.ARST
Troubleshooting
13