Parameters
Write 1000 to execute stop command, which is the same as DI.STP.
When reading P5.007, if the command is incomplete, the drive reads the current command (1 - 99).
If the command is complete, the drive reads the current command +10000. If the command is complete,
8
DO.TPOS is on, and motor position is reached, the drive reads the current command +20000.
Commands triggered by DI are also applicable.
Example:
If the value read is 3, it means PR#3 is incomplete. If the value read is 10003, it means PR#3 completed,
but the motor has not reached the target position yet. If the value read is 20003, it means PR#3
completed and the motor reached the target position.
P5.008
Default:
Unit:
Format:
Settings:
In PR mode, if the motor rotates in the forward direction and its feedback position exceeds the value of
P5.008, AL283 occurs.
P5.009
Default:
Unit:
Format:
Settings:
In PR mode, if the motor rotates in the reverse direction and its feedback position exceeds the value of
P5.009, AL285 occurs.
P5.010★■
Default:
Unit:
Format:
Settings:
Data size (N x 32 bits) means size N of data array.
8-118
Forward software limit
2147483647
PUU
DEC
Reverse software limit
-2147483648
PUU
DEC
Data array - data size
-
-
DEC
Control mode: PR
Setting range: -2147483648 to +2147483647
Data size:
32-bit
Control mode: PR
Setting range: -2147483648 to +2147483647
Data size:
32-bit
Control mode: All
Setting range: Read-only
Data size:
16-bit
ASDA-A3
Address: 0510H
0511H
Address: 0512H
0513H
Address: 0514H
0515H