ASDA-A3
When the load ratio is 160%, the overload (AL006) protection counter continues to increase.
1.
When the load ratio is 100%, the operating level is leveled off.
2.
When the load ratio is 40%, the overload (AL006) protection counter continues to decrease.
3.
Example 2:
Overload (AL006)
protection counter
100%
0%
As shown in the figure above, the load ratio affects whether the load is accumulated. When the load
accumulates over 100%, the operating time must be taken into consideration, or else AL006 occurs.
If the load ratio is below 100%, you do not need to consider the operating time.
PM.020▲
Default:
100
Unit:
%
Format:
DEC
Settings:
Refer to the description of PM.019.
PM.021
PM.022▲●
Default:
0
Unit:
-
Format:
DEC
T1
Load decrease gain
Reserved
Motor temperature sensor
AL006 occurs
Servo Off
T2
T3
Applicable motor: All
Setting range:
0 - 600
Data size:
16-bit
Applicable motor: Linear motor, third-party rotary motor
Setting range:
0 - 3
Data size:
16-bit
Parameters
Load ratio
Load ratio
Operating level
160%
140%
40%
Time
Address: FD28H
FD29H
Address: FD2CH
FD2DH
8
8-205