6 Calibration
6.5.3 Calibrating axis 3 and axis 4
Continued
Checking and finalizing the calibration
1
2
3
Continues on next page
816
Action
DANGER
Always remember to remove the calibration tools
from the robot before jogging axes to zero position
during calibration.
Release the brakes and manually rotate the axis
to apart the calibration pins from each other. This
is done to avoid damage on the pins if incorrect
operation should occur during next step of jog-
ging.
Jog axes 3 and 4 to zero degree using the Flex-
Pendant.
© Copyright 2019-2022 ABB. All rights reserved.
Note
Product manual - IRB 910INV
3HAC068055-001 Revision: K