Co: Fixed Value 2 [%] / Fixed Value 2 [%]; Co: Fixed Values [%] / Fixed Values [%]; Co: Fixed Value M [Nm] / Fixed Value M [Nm] - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

p2901[0...n]

CO: Fixed value 2 [%] / Fixed value 2 [%]

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-10000.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
See also: p2900, p2930
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
r2902[0...14]

CO: Fixed values [%] / Fixed values [%]

Access level: 3
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Display and connector output for frequently used percentage values.
Index:
[0] = Fixed value +0 %
[1] = Fixed value +5 %
[2] = Fixed value +10 %
[3] = Fixed value +20 %
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency:
See also: p2900, p2901, p2930
Note
The signal sources can, for example, be used to interconnect scalings.
p2930[0...n]

CO: Fixed value M [Nm] / Fixed value M [Nm]

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-100000.00 [Nm]
Description:
Setting and connector output for a fixed torque value.
Dependency:
See also: p2900, p2901, r2902
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
10000.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated: -
Scaling: p2003
Unit selection: -
Max:
100000.00 [Nm]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 1021
Factory setting:
0.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 1021
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 1021
Factory setting:
0.00 [Nm]
825

Advertisement

Table of Contents
loading

Table of Contents