Note
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1024

CO: Fixed speed setpoint effective / Speed fixed setp

Access level: 3
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Display and connector output for the selected and active fixed speed setpoint.
This setpoint is the output value for the fixed speed setpoints and must be appropriately interconnected (e.g. with the
main setpoint).
Recommendation:
Interconnect the signal with the main setpoint (CI: p1070 = r1024).
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
See also: p1070
Note
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1025.0
BO: Fixed speed setpoint status / n_setp_fix status
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and binector output for the status when selecting the fixed speed setpoints.
Bit field:
Bit
00
Dependency:
See also: p1016
Note
For bit 00:
When the fixed speed setpoints are directly selected (p1016 = 1), this bit is set if at least 1 fixed speed setpoint is
selected.
p1030[0...n]

Motorized potentiometer configuration / Mop configuration

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration for the motorized potentiometer.
Bit field:
Bit
00
01
02
03
04
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Signal name
Fixed speed setpoint selected
Signal name
Data save active
Automatic mode ramp-function generator active
Initial rounding-off active
Save in NVRAM active
Ramp-function generator always active
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 3001, 3010,
3011
Factory setting:
- [rpm]
Data type: Unsigned8
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
3011
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: 3020
Factory setting:
0000 0110 bin
0 signal
FP
No
-
No
-
No
-
No
-
No
-
467