p2252

Technology controller configuration / Tec_ctrl config

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration of the technology controller.
Bit field:
Bit
04
05
06
07
08
Dependency:
For bit 04 = 0:
The setting is only effective when the PID controller is deactivated.
CAUTION
For bit 04 = 1:
The PID controller can oscillate if the ramp-up and ramp-down times of the speed setpoint channel are not taken into
account when setting controller parameters p2280 and p2285.
Note
For bit 04 = 0:
The ramp-function generator in the speed setpoint channel is bypassed when the technology controller is operational.
As a consequence, ramp times p1120, p1121 are not taken into consideration when configuring the controller.
For bit 04 = 1:
The ramp-function generator in the speed setpoint channel is not bypassed when the technology controller is
operational.
As a consequence, the ramp-up and ramp-down times (p1120, p1121) remain effective, and must be taken into
account as controlled system variables when setting the PID controller parameters (p2280, p2285).
The enable ramps of the PID controller are ensured in this setting by p1120, p1121 as well as rounding functions p1130
and p1131. The ramp-up/ramp-down time of the PID controller limiting p2293 must be set appropriately shorter, as
otherwise this has an impact on the speed setpoint channel.
For bit 05 = 0:
The integral component of the PID controller is held if a skip band or the minimum speed range is passed through in
the speed set point channel.
This prevents the speed from oscillating between the edges of the skip band.
For bit 05 = 1:
The setting is only effective if a skip band is no longer active.
The integral component of the PID controller is not held in the range of the skip speeds.
The skip band is passed through even for small system deviations and low controller gain factors. In so doing, the
controller integral time must be selected large enough so that no undesirable speed oscillations occur between the skip
band edges.
The influence of a minimum speed p1080 on the integration behavior can be reduced by raising the lower PID controller
limit to p1080 / p2000 * 100%.
For bit 06 = 1:
In r2349, bit 10 and bit 11 are not displayed when reaching internal limits (e.g. for OFF1/3).
p2253[0...n]

CI: Technology controller setpoint 1 / Tec_ctrl setp 1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Signal name
Ramp-up/ramp-down function generator bypass
Integrator active for skip speeds
Internal controller limit not displayed
Activate Kp adaptation
Activate Tn adaptation
Calculated: CALC_MOD_ALL Data type: Unsigned16
Scaling: -
Unit selection: -
Max:
-
1 signal
Deactivated
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Dynamic index: -
Function diagram: -
Factory setting:
0000 0000 0000 0000 bin
0 signal
FP
Activated
-
No
-
No
-
No
7958
No
7958
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 7958
Factory setting:
0
611