z = 2: File MOTSLM.ACX
z = 3: File ENCDATA.ACX
z = 4: File FILTDATA.ACX
z = 5: File BRKDATA.ACX
z = 6: File DAT_BEAR.ACX
z = 7: File CFG_BEAR.ACX
z = 8: File ENC_GEAR.ACX
z = 9: File CFG_BRK.ACX
z = 10: File THERMMOTMOD.ACX
z = 11: File MAPPING.ACX
z = 12: File LOADGEAR.ACX
z = 13: File MOTRSM.ACX
Remedy:
For the file on the memory card involved, restore the status originally supplied from the factory.
A01020
Writing to RAM disk unsuccessful
Message value:
-
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A write access to the internal RAM disk was unsuccessful.
Remedy:
Adapt the file size for the system logbook to the internal RAM disk (p9930).
See also: p9930 (System logbook activation)
F01023
Software timeout (internal)
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software timeout has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
F01030
Sign-of-life failure for master control
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Reaction:
Vector: OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
For active PC master control, no sign-of-life was received within the monitoring time.
The master control was returned to the active BICO interconnection.
Remedy:
Set the monitoring time higher at the PC or, if required, completely disable the monitoring function.
For the commissioning software, the monitoring time is set as follows:
<Drive> -> Commissioning -> Control panel -> Button "Fetch master control" -> A window is displayed to set the
monitoring time in milliseconds.
Notice:
The monitoring time should be set as short as possible. A long monitoring time means a late response when the
communication fails!
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1375