Temperature sensor
+ temp
2 mA
X520.5
+
X520.6
-
KTY/PT1000/PTC
- temp
threshold 1650 Ohm
PTC
KTY
PT1000
<1> p3665
= 0: No sensor
= 1: PTC
= 2: KTY
= 6: PT1000
<2> A fault or alarm in the temperature evaluation of the VSM is communicated to the downstream evaluation using special temperature values.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approximate 188.6 °C.
<4> PTC:
A value > 250 °C de-activates the alarm or fault.
KTY/PT1000: A value > 188.6 °C de-activates the alarm or fault.
<5> Can only be used with chassis infeeds.
<6> The VECTOR drive object is assigned a dynamic index (p0150).
1
2
DO: A_INF, S_INF, VECTOR
Voltage Sensing Module (VSM) - Temperature evaluation
Sensor type
Hardware
smoothing 1 s
A
Resistance
calculation
D
PTC resistor
1
0
0
No sensor
-50 °C
250 °C
1
188.6 °C
R
<3>
T
-140 °C
188.6 °C
R
<3>
T
-70 °C
3
4
p3665 (0)
Software smoothing
<6>
<1>
0.5 s
Sensor type
<6>
p3665 (0)
Overtemperature hysteresis
p3669
<6>
<1>
0
1
2
6
Alarm is not present
Alarm is present
-300 °C
5
fp_9886_54_eng.vsd
11.02.16 V04.08.00
Overtemperature alarm threshold
0...301 [°C]
<4>
<6>
p3667[0] (150)
1
r3664.0
0
A34211
"Temperature alarm
threshold exceeded"
1
r3664.1
0
F34207
"Temperature fault
threshold exceeded"
Overtemperature fault threshold
<4>
0...301 [°C]
<6>
p3668[1] (180)
<2>
Fault F34920
temperature sensor evaluation
0
VSM temp_act
r3666
1
6
7
Function diagram
S120/S150/G130/G150
4000.00 μs
<5>
8
- 9886 -