4 Faults and alarms
4.2 List of faults and alarms
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved the project data using the commissioning software, carry out a new download for your project.
Save using the function "Copy RAM to ROM" or with p0977 = 1.
This means that the parameter files are again completely written into the non-volatile memory.
Note:
If the project data have not been backed up, then a new first commissioning is required.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01038 (A)
ACX: Loading the parameter back-up file unsuccessful
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
An error has occurred when downloading PSxxxyyy.ACX or PTxxxyyy.ACX files from the non-volatile memory.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2:
255: Incorrect drive object type.
254: Topology comparison unsuccessful -> drive object type was not able to be identified.
Reasons could be:
- incorrect component type in the actual topology
- Component does not exist in the actual topology.
- Component not active.
Additional values:
Only for internal Siemens troubleshooting.
Byte 4, 3:
Only for internal Siemens troubleshooting.
Remedy:
- if you have saved the project data using the commissioning software, download the project again. Save using the
function "Copy RAM to ROM" or with p0977 = 1. This means that the parameter files are again completely written to
the non-volatile memory.
- replace the memory card or Control Unit.
For byte 2 = 255:
- correct the drive object type (see p0107).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
1378
Propagation:
LOCAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150